Enclosed Distribution Capacitor Bank

Options & Ordering Information

To request a quotation or order a Gilbert Electrical Systems MELP transclosure capacitor assembly, use the tables below to construct a catalog number which will describe your requirement.

Table 1 - Specifies the code describing the installed Kvar and system voltage.
Table 2 - Specified the code describing the required bank connection.
Table 3 - Specified the code describing switch options.
Table 4 - Specifies the code for incoming cable configuration.
Table 5 - Specifies the code that describes the optional equipment available as standard.

  Table 1 - Codes for Three-Phase Installed Kvar and Systems Voltage
Capacitor Line-to-Line
Voltage
Capacitor Bank Three-Phase Kvar Rating
50 100 150 200 250 300 400 450 600 900 1200 1500 1800 2400 3000
Code
2400 A01 B01 C01 D01 E01 F01 G01 H01 I01 J01 K01 L01 M01 N01 Note 3
2770 A02 B02 C02 D02 E02 F02 G02 H02 I02 J02 K02 L02 M02 N02 O02
4160 A03 B03 C03 D03 E03 F03 G03 H03 I03 J03 K03 L03 M03 N03 O03
4800 A04 B04 C04 D04 E04 F04 G04 H04 I04 J04 K04 L04 M04 N04 O04
6600 A05 B05 C05 D05 E05 F05 G05 H05 I05 J05 K05 L05 M05 N05 O05
7200 A06 B06 C06 D06 E06 F06 G06 H06 I06 J06 K06 L06 M06 N06 O06
12470 A07 B07 C07 D07 E07 F07 G07 H07 I07 J07 K07 L07 M07 N07 O07
13200 A08 B08 C08 D08 E08 F08 G08 H08 I08 J08 K08 L08 M08 N08 O08
13800 A09 B09 C09 D09 E09 F09 G09 H09 I09 J09 K09 L09 M09 N09 O09
14400 Note 2 B10 C10 D10 E10 F10 G10 H10 I10 J10 K10 L10 M10 N10 O10

Note 1: 50 Kvar, 100 Kvar, 200 Kvar, 250 Kvar and 400 Kvar three-phase capacitor banks will utilize three-phase capacitor units. All other capacitor banks will use single phase capacitor units.
Refer to Table 6 for standard single phase capacitor units used in MELP capacitor banks.
Refer to Table 7 for standard three phase capacitor units used in MELP capacitor banks.
Note 2: Consult Gilbert Electrical Systems for this rating.
Note 3: Fixed capacitor bank only. Consult Gilbert Electrical Systems for a switched bank alternative.

Table 2 - Bank Connections  
Description Code
 Ungrounded WYE (for 3 phase , 3 wire or 4 wire systems)  U
 Grounded WYE (for 3 phase, 4 wire multi-grounded systems only)  G
 Delta (for 3 phase, 3 wire systems only)  D

Table 3 - Switch Options  
Description Code
 Switched with three single phase 200 amp oil switches. Refer to Table 9 for switch information.  F
 Switched with three single phase 200amp vacuum switches. Refer to Table 9 for switch information.  V
 Switched with three phase vacuum contactor. Refer to Table 9 for switch information.  C
 Fixed. No Switches  N

Table 4 - Incoming Cable Configurations  
Description Code
 Live-front underground entrance that includes provisions for three single phase terminators (terminators not included)  LF
 Dead-front radial feed using three 200 amp bushing wells. These devices are to be used for visible disconnection only; they are not designed for capacitor load switching.  DF
 Dead-front loop feed using six 200 amp bushing wells. These devices are to be used for visible disconnection only; they are not designed for capacitor load switching.  DL
 
Table 5 - Optional Equipment  
Description Code
 Group Operated three phase disconnect switch with front operator. This switch is not intended for load breaking.  S1
 Group Operated three phase disconnect switch with side operator. This switch is not intended for load breaking.  S2
 Group Fusing in addition to capacitor fuses.  GF
 Current Limiting Reactors, 40 microhenries, 160 amp, GES catalog number 43893.  R
 Surge arresters - Set of 3 distribution class.  SA
 Key Interlock Scheme  K
 Penta-head bolt doors  P
 Control Power Transformer with 120 VAC secondary  T
 Unbalance Detection  U
 Optional Equipment not required.  Z
Controller (*Select One):  
 Voltage  VC
 Current  CC
 Temperature  TC
 Time Clock  TT
 Power Factor  PFC
 Var  VAR
 Manual  MAN
Paint options (*Select One):
 
 Guardian Green  GG
 Gray ANSI 61  GR
 Light Gray  LG
Enclosure (*Select One):  
 11 gauge mild steel (standard)  MS
 pickled and oil steel  GS
 304L Stainless Steel  SS
 Aluminum 5052-H32  AL

Constructing a Catalog Number

The chart below shows how to construct the catalog number for the series MELP capacitor assembly with the following requirements:

  • 7200/12470 volt 2400 kvar three phase
  • Three phase, three wire system - ungrounded WYE connected capacitor bank
  • Switched with 200 amp vacuum switches
  • Control power transformer
  • Manual controls
  • Live-front with provisions for three single conductor terminators
  • Key-interlock scheme
  • Guardian Green paint
  • Pickled and oil steel enclosure painted with DuPont Power Coat paint.
EDC - Basic letters for series MELP metal enclosed capacitor assembly
NO6 - Installed three phase kvar and voltage rating code; select from Table 1.
- Bank Connection Code ; select from Table 2
- Switch option code; select from Table 3
LF - Incoming cable configuration; select from Table 4
K-T-MAN-GG-GS - Optional equipment code; select from Table 5

The complete catalog number would be:
EDC-N06UVLF-K-T-MAN-GG-GS